China Installation of XLMS1-RC Residual Pressure Controller Inside the Positive Pressure Fan - China Supplier
China Installation of XLMS1-RC Residual Pressure Controller Inside the Positive Pressure Fan - China Supplier

Installation of XLMS1-RC Residual Pressure Controller Inside the Positive Pressure Fan

Price:Negotiable
Industry Category: Machinery & Equipment/Fans & Ventilation Equipment/Other Fans & Ventilation Equipment
Product Category:
Brand: 亞川科技
Spec: XLMS1-RC


Contact Info
  • Add:西安市翠華南路60號, Zip: 710061
  • Contact: 仵小玲
  • Tel:13891834587
  • Email:704151787@qq.com

Other Products

Description
Additional Information

XLMS1-RC Residual Pressure Controller

XLMS1-RC Residual Pressure Controller Functions:

Monitors the pressure working status and fault alarm information of all monitored areas in real time, and uploads the working status and alarm information to the control room XLMS1-H200 residual pressure monitoring host;

Residual Pressure Monitoring System Product Composition:

XLMS1-RC Residual Pressure Controller

XLMS1-RS Residual Pressure Sensor

XLMS1-24V-NM Electric Bypass Valve Pressure Relief Valve

XLMS1-H200 Residual Pressure Monitoring Host

The residual pressure monitoring system mainly consists of: residual pressure monitor, residual pressure detector, residual pressure controller, electric actuator, air tube, and air tube end panel.

Residual pressure value in smoke-proof stairwells: 40–50Pa

Residual pressure value in anterooms and combined anterooms: 25–30Pa.

★ When the pressure difference exceeds the set value (50Pa for stairwells, 30Pa for anterooms), the residual pressure detector sends an alarm signal to the residual pressure controller, which then controls the electric actuator to open the bypass valve and begin pressure relief.

★ When the pressure difference reaches the set value range (40Pa for stairwells, 25Pa for anterooms), the residual pressure controller controls the electric actuator to close the bypass valve, completing the pressure relief.

Residual pressure controller aliases: Also known as residual pressure controller, pressure relief controller, residual pressure zone controller, air damper controller, bypass valve controller, positive pressure air damper controller, residual pressure control unit, etc.

Consultation Information

For more product information, please call our company.

Contact: Manager Wu

Phone: 13891834587 (same number for WeChat)

QQ: 407693430

Email: 407693430@qq.com

Technical Parameters

Input power: AC220V 50Hz (taken from the pressurized fan control box)

Output voltage: DC24V

Communication method: RS485 standard protocol

Communication distance: Reliable communication up to 500m, capable of parallel connection and management of 128 residual pressure sensors

Alarm function: Equipped with alarm display function

Intelligent residual pressure threshold: Intelligently sets the allowable residual pressure value for evacuation doors, controlling the opening and closing angle of the pressure relief valve.

Product Features

1: Fully meets and exceeds the functional requirements of national standards such as GB51251 "Technical Standard for Building Smoke Control and Exhaust Systems" and GB850016 "Code for Fire Protection Design of Buildings";

2: Uses RS485 communication and independent power supply with XLMS1-RS residual pressure sensors, communication lines use RVS-2x1.5mm2 twisted pair, power lines use RV-2x2.5mm2 power lines, capable of parallel (T-connection) connection and management of 128 XLMS1-RS residual pressure sensors within 500 meters;

3: Uses centralized power supply to provide DC24V safe voltage to XLMS1-RS residual pressure sensors, ensuring system stability and personal safety;

4: Monitors the pressure working status and fault alarm information of all monitored areas in real time, and uploads the working status and alarm information to the control room XLMS1-H200 residual pressure monitoring host;

5: Precisely and continuously controls the opening and closing angle of the electric bypass pressure relief valve, maintaining the residual pressure value within the required standard range;

6: Can monitor the operating status and fault status of positive pressure fans;

7: Supports on-site online programming to meet customer on-site usage requirements;

8: Can be paired with the monitoring host to flexibly build large-capacity residual pressure monitoring systems, adapting to building application needs;

Industry Category Machinery & Equipment/Fans & Ventilation Equipment/Other Fans & Ventilation Equipment