China PSL691U Line Protection and Control Device - China Supplier China PSL691U Line Protection and Control Device - China Supplier China PSL691U Line Protection and Control Device - China Supplier China PSL691U Line Protection and Control Device - China Supplier China PSL691U Line Protection and Control Device - China Supplier

PSL691U Line Protection and Control Device

Price:100
Industry Category: Chemicals/Chemical Intermediates/Intermediate Compounds
Product Category:
Brand: 國(guó)電南自
Spec: PSL691U


Contact Info
  • Add:宜昌市西陵區(qū)港城路6號(hào), Zip: 443100
  • Contact: 蔣應(yīng)娟
  • Tel:18062398092
  • Email:3052844599@qq.com

Other Products

Description
Additional Information

Guodian Nanzi PSL691U Line Protection and Control Device

1. Overload Alarm
When the current of any phase exceeds the set value, after a delay, the device issues an alarm signal.
2. Reclosing
When all three conditions are met—reclosing function enabled, circuit breaker in closed position for 15 seconds, and spring not charged contact open—the reclosing charging is completed (i.e., the reclosing is ready to operate). After reclosing charging is completed, the operation light flashes; if reclosing is not ready, the operation light remains steady and does not flash.
After reclosing charging is completed, once a protection trip or unintended trip occurs, the reclosing is initiated after the reclosing delay.
After reclosing is initiated, it operates based on the selection of no-voltage check, synchronism check, or no-check.
a) Synchronism check reclosing condition: | ∠Ux -∠Uab - ∠φ | ≤ synchronism check closing angle
Note: ∠Ux is the line voltage angle;
∠Uab is the busbar voltage Uab angle;
∠φ is the angle by which Ux leads Uab under normal conditions due to phase differences or system wiring.
b) No-voltage check reclosing condition: Ux ≤ no-voltage check set value
If Ux is greater than the no-voltage check set value, it automatically switches to synchronism check reclosing.
c) No-check reclosing: No judgment is made on the magnitude or phase angle of Ux, and the circuit breaker is closed directly.
If reclosing cannot be completed within 10 seconds after initiation, the reclosing process is automatically terminated.
When manual tripping, remote tripping, overload, underfrequency load shedding, or undervoltage load shedding occurs, the device automatically blocks the reclosing function.
3. Synchronism Check Manual Closing
When the relationship between Ux and Uab meets the synchronism check reclosing condition and synchronism check manual closing is enabled, contacts 4X19 and 4X21 of the device close. Users can connect contacts 4X19 and 4X21 in series into the manual closing circuit to achieve synchronism check for manual closing.
4. Closing Acceleration Protection
During manual closing, remote closing, or reclosing operation, if a fault is encountered, the device is equipped with acceleration protection to quickly clear the fault. This protection monitors the current within 3 seconds after the circuit breaker changes from open to closed position. If the current of any phase exceeds the set value, the device trips after a short delay. After 3 seconds, the acceleration protection is automatically disabled.
5. Underfrequency Load Shedding
When the system frequency is below the set value, after a delay, the device trips.
The underfrequency load shedding function can include undervoltage blocking or rate-of-change-of-frequency (df/dt) blocking to prevent maloperation.
Undervoltage blocking criterion: When Uab, Ubc, and Uca are all below the undervoltage blocking set value, underfrequency load shedding is blocked.
Rate-of-change-of-frequency blocking criterion: When Δf/Δt exceeds the rate-of-change-of-frequency blocking set value, underfrequency load shedding is blocked.
6. Undervoltage Load Shedding
When all three line voltages are below the set value, after a delay, the device trips.
The undervoltage load shedding function is blocked if any of the following conditions is met:
a) Any line voltage < 30V
b) ΔU/Δt > voltage rate-of-change blocking set value, where ΔU/Δt is the change in voltage per second for any phase. When the line voltage is below the set value, the voltage rate-of-change is maintained. When the line voltage exceeds the set value, the voltage rate-of-change is updated in real time.
c) All three-phase currents < 0.1In
d) Circuit breaker in open position
e) PT circuit broken
f) Negative-sequence voltage > 5V

Industry Category Chemicals/Chemical Intermediates/Intermediate Compounds
Product Category
Brand: 國(guó)電南自
Spec: PSL691U
Stock: 100
Manufacturer:
Origin: China / Jiangsu / Nanjingshi
About Toocle.com - Partner Programme - Old Version
Copyright ? Toocle.com. All Rights Reserved.
(浙)-經(jīng)營(yíng)性-2023-0192
ChatGlobal Chat Now 祁阳县| 福海县| 喀什市| 张家港市| 深水埗区| 禹州市| 三门县| 徐汇区| 拜城县| 龙州县| 铜川市| 上饶县| 武胜县| 桓仁| 宾川县| 东乌珠穆沁旗| 清水河县| 蛟河市| 罗江县| 忻州市| 敖汉旗| 公主岭市| 东方市| 凤冈县| 电白县| 深水埗区| 休宁县| 洪洞县| 卓尼县| 吉林省| 安泽县| 三原县| 托里县| 镇平县| 宁波市| 新民市| 东丰县| 重庆市| 武陟县| 法库县| 正安县|