尤物视频污,99热99热99超碰,精品久久久久女少妇,少妇精品无码,日B视屏久久香色,亚洲美女午夜福利av,国产美女被操,国产九九精品,国产久久色情

China ISA-381G Station Service Transformer Protection and Control Device - China Supplier
China ISA-381G Station Service Transformer Protection and Control Device - China Supplier China ISA-381G Station Service Transformer Protection and Control Device - China Supplier

ISA-381G Station Service Transformer Protection and Control Device

Price:¥888
Industry Category: Electronic Components & Supplies/Transformers/Other Transformers
Product Category:
Brand: 長(zhǎng)園深瑞
Spec: ISA-381G


Contact Info
  • Add:宜昌市西陵區(qū)港城路6號(hào), Zip: 443100
  • Contact: 蔣應(yīng)娟
  • Tel:18062398092
  • Email:3052844599@qq.com

Other Products

Description
Additional Information

Changyuan Shenru ISA-381G Station Transformer Protection, Measurement and Control Device


The ISA-381G device implements protection, measurement and control, and operational functions for station/grounding transformers (supports 220V voltage monitoring).
ISA-381G Model and Function Description Table
Model Function Description
ISA-381GA Suitable for small resistance grounding systems, supports 220V voltage monitoring
ISA-381GB Suitable for ungrounded systems, supports 220V voltage monitoring
ISA-381GC Suitable for ungrounded systems or small resistance grounding systems

Protection Principles
Phase Current Over-Limit Recording Element
The phase current over-limit recording element has an independent over-limit threshold setting d797, and records the over-limit condition of each phase current separately, generating independent phase current over-limit records, including the start time, duration, and maximum current of the over-limit condition for each phase.
1) Per-phase recording facilitates detailed and comprehensive documentation of disturbance processes.
2) This record is not used for alarms, only for disturbance analysis.
3) The device interface provides a function to view phase current over-limit records.
4) The setting of d797 should avoid the maximum load current value (to prevent unnecessary frequent recording) and ensure sufficient sensitivity for smaller fault currents.
Three-Stage Overcurrent Protection
Three-stage overcurrent protection includes instantaneous overcurrent, Stage I overcurrent, and Stage II overcurrent protection. Each can be independently enabled or disabled, with current and time settings adjustable independently. The principles of the three stages are the same; Figure 4-2-1 shows the logic diagram for Stage I overcurrent protection.
Low-Voltage Side Zero-Sequence Overcurrent Protection
The low-voltage side zero-sequence protection includes two independently configurable definite-time zero-sequence overcurrent protections and one inverse-time zero-sequence overcurrent protection. The logic for Stage I and Stage II zero-sequence overcurrent protections is identical, except for setting codes and event codes. The logic is shown in Figure 4-2-2.
Low-Voltage Side Inverse-Time Zero-Sequence Overcurrent Protection
The ISA-381GA/B/C devices each include one inverse-time zero-sequence overcurrent protection, offering three operating characteristics: general inverse-time, very inverse-time, and extremely inverse-time. If all three are enabled simultaneously, the priority from highest to lowest is: extremely inverse-time > very inverse-time > general inverse-time.
High-Voltage Side Zero-Sequence Overcurrent Protection
Note: In "Configuration" - "Manufacturer Settings" - "Zero-Sequence Current Collection Method," the high-side zero-sequence current 3Iol and 3Iog can be set to "self-generated" or "external input." The default is "external input." When set to "self-generated," the protection zero-sequence current is synthesized from the three-phase protection currents. For telemetry, 3Iol in the 381GB is also synthesized from the three-phase protection currents, while the 381GC uses the three-phase measurement currents for synthesis.
1) Zero-Sequence Overcurrent Protection for Small Resistance Grounding Systems (ISA-381GA/ISA-381GC)
For small resistance grounding systems, the ISA-381GA/ISA-381GC devices provide three-stage high-voltage side zero-sequence overcurrent protection as backup protection for bus ground faults. The principles of the three stages are the same; Figure 4-2-6 shows the logic for Stage I zero-sequence overcurrent protection.

Industry Category Electronic Components & Supplies/Transformers/Other Transformers
Product Category
Brand: 長(zhǎng)園深瑞
Spec: ISA-381G
Stock: 1000
Manufacturer:
Origin: China / Guangdong / Shenshi
About Toocle.com - Partner Programme - Old Version
Copyright ? Toocle.com. All Rights Reserved.
(浙)-經(jīng)營(yíng)性-2023-0192
ChatGlobal Chat Now SHOW| 东莞市| 大埔县| 鄂伦春自治旗| 丹凤县| 扎囊县| 修水县| 清新县| 大石桥市| 白沙| 黔东| 克山县| 萍乡市| 乐业县| 昌黎县| 安丘市| 高唐县| 灵山县| 西和县| 牟定县| 五峰| 巢湖市| 浦江县| 株洲市| 团风县| 翁源县| 郑州市| 民县| 响水县| 五台县| 新绛县| 江孜县| 保康县| 行唐县| 陕西省| 玉溪市| 德阳市| 宁乡县| 鄯善县| 东乡县| 镇坪县|